有(you)(you)(you)的管道設(she)計(ji)人(ren)員因不清楚(chu)靜電(dian)(dian)接(jie)地(di)范(fan)圍而引起(qi)設(she)計(ji)事(shi)故,因此著重講述。我國(guo)管道靜電(dian)(dian)接(jie)地(di)和跨接(jie)相關標準(zhun)規(gui)范(fan)有(you)(you)(you)GB12158《防止靜電(dian)(dian)事(shi)故通用導則》、HG/T 20675《化(hua)工(gong)企(qi)業靜電(dian)(dian)接(jie)地(di)設(she)計(ji)規(gui)程(cheng)(cheng)》、SH/T 3097《石油化(hua)工(gong)靜電(dian)(dian)接(jie)地(di)設(she)計(ji)規(gui)范(fan)》等,GB 50235《工(gong)業金(jin)屬(shu)管道工(gong)程(cheng)(cheng)施工(gong)規(gui)范(fan)》等規(gui)范(fan)也有(you)(you)(you)專門的章(zhang)節(jie)對管道靜電(dian)(dian)接(jie)地(di)實施作出規(gui)定(ding)。ASME、PIP等國(guo)外標準(zhun)規(gui)范(fan)也有(you)(you)(you)具體(ti)規(gui)定(ding),國(guo)內外一些大型公司(si)和工(gong)程(cheng)(cheng)建設(she)單位,對管道靜電(dian)(dian)接(jie)地(di)設(she)計(ji)有(you)(you)(you)企(qi)業級的規(gui)定(ding)。
①. 位于(yu)爆炸(zha)(zha)(zha)和火(huo)災危(wei)險區(qu)內的管道應進行靜電(dian)(dian)接地。在爆炸(zha)(zha)(zha)和火(huo)災危(wei)險區(qu)內,可能(neng)存在可燃(ran)(ran)氣體(ti)和可燃(ran)(ran)粉(fen)塵(chen)積聚,如果產(chan)生電(dian)(dian)火(huo)花,可能(neng)引(yin)起火(huo)災或(huo)(huo)爆炸(zha)(zha)(zha)事故。為了防止在電(dian)(dian)氣設(she)施使用(yong)過程中產(chan)生電(dian)(dian)火(huo)花,引(yin)燃(ran)(ran)或(huo)(huo)引(yin)爆可燃(ran)(ran)氣體(ti)或(huo)(huo)可燃(ran)(ran)粉(fen)塵(chen),爆炸(zha)(zha)(zha)和火(huo)災危(wei)險區(qu)內的強、弱電(dian)(dian)設(she)施均需要選用(yong)防爆型。
②. 氧(yang)氣(qi)管道(dao)應進行靜電接地(di)。氧(yang)氣(qi)是一種特殊(shu)的介質,其(qi)本身不燃燒,卻是強氧(yang)化劑,在純氧(yang)的環境中(zhong),鋼管會被點(dian)燃。因此(ci)雖然氧(yang)氣(qi)不屬于可燃介質,但純氧(yang)管道(dao)必(bi)須良(liang)好接地(di)。
③. 氣固管道(dao)應進行靜電(dian)接(jie)地。氣固管道(dao)在運行過程中會產生大量(liang)靜電(dian),必須保證管道(dao)良好(hao)接(jie)地,防止大量(liang)靜電(dian)集聚(ju)。
④. 平(ping)行敷設(she)(she)的管(guan)道,凈距小于(yu)100mm時(shi),應每(mei)隔20m,設(she)(she)置(zhi)靜(jing)電跨接。近距離平(ping)行敷設(she)(she)的管(guan)廊,為保證兩(liang)根(gen)管(guan)道等(deng)電位,需要每(mei)隔20m設(she)(she)置(zhi)跨接。
⑤. 管(guan)(guan)道(dao)(dao)進(jin)出裝(zhuang)(zhuang)置界區(qu)處應進(jin)行(xing)靜電(dian)接(jie)地,防止界外管(guan)(guan)道(dao)(dao)和(he)裝(zhuang)(zhuang)置內管(guan)(guan)道(dao)(dao)間電(dian)荷的(de)相互(hu)轉移。